Services

Pulse Controller Malfunction

Check whether the controller indicates each contact /check the output of each terminal.

Incorrect Setting of the Pulse Jet System

Increase pulse jet frequency / Low compressed air pressure; raise pressure, inspect the dryer and clean it if necessary, check for blockages in pipelines.

Main Causes and Troubleshooting for Low Fan Motor Current / Low Air Volume

  1. High differential pressure of the dust collector.
  2. Reversed installation of fan and motor pulleys: Refer to drawings and reinstall the pulleys correctly.
  3. Pipeline blockage due to dust accumulation: Clean the pipeline and check the gas flow velocity.
  4. Fan damper closed: Open the damper and lock it in the open position.
  5. Dust collector poppet valve closed: Inspect the air circuit and open the valve plate.
  6. Excessively high system static pressure: Measure static pressure at both ends of the fan and verify against design specifications, adjust as required. Check pipelines for high flow velocity and replace the original defective design.
  7. Fan operating outside design requirements: Inspect the fan inlet structure to ensure stable airflow. Check blades for wear, repair or replace as needed.
  8. Fan reverse rotation: Reverse the wiring connections on the motor.

Excessive Secondary Dust Re-entrainment

Drain the hopper continuously; perform ash cleaning for each row of filter bags/cartridges in a random sequence instead of sequential cleaning. Inspect the inlet baffle and ensure it is clean.

Pulse Jet Valve Malfunction

Check the diaphragm valve /inspect the control solenoid valve.

Incorrect Differential Pressure Reading

Clean the pressure tap /inspect the air tube for cracks /check the differential pressure gauge.

Filter Bag Clogging

Condensation on filter bags (see below); send the filter bags to the laboratory for cause analysis.
Dry and ash-clean the filter bags, or replace them, reduce air volume, increase compressed air pressure, raise ash cleaning frequency, and inject neutral conditioning powder to form a protective layer and porous loose primary cake.

 LINKS:

 TEL:022-27211006 Email:tjtmjn@163.com

 Copyright © 天津天迈节能设备有限公司 Copyright